1. |
The exhibitor/Contactor must appoint a licensed electrical contractor for carrying
out the internal wiring within the stall. Exhibitor/Contractor to submit a photo
copy of the contractor license to the council. Along with Form No.2 with signed
acknowledgment. |
|
|
|
|
|
|
2. |
The contractor to appoint a licensed supervisor at site for executing the work. |
|
|
|
|
|
|
3. |
It is mandatory to use only ISI mark new material for doing the electrical installation. |
|
|
|
|
|
|
4. |
The council contractor will lay the cables and will provide an MCB distribution
board for
distributing power within the stall as per the drawing submitted by Exhibitors/Contractor. |
|
|
|
|
|
|
5. |
The wires shall be PVC insulated 1100 V insulated of copper. |
|
|
|
|
|
|
6. |
For lighting circuit the wire shall be 3x2.5sq.mm copper wire. For 16A power point.
3X4sq.mm
PVC insulated copper wire shall be used. |
|
|
|
|
|
|
7. |
Wire shall be run in a safe manner through coundit or casing capping. No wire shall
hang lose. |
|
|
|
|
|
|
8. |
Wire shall be terminated using crimping lugs. |
|
|
|
|
|
|
9. |
Entire installation shall be done in a safe manner. |
|
|
|
|
|
|
10. |
The type of light shall be CFL or tube light & halogen lights will not be permitted. |
|
|
|
|
|
|
11. |
The load connected to power point shall be suitable for the socket. |
|
|
|
|
|
|
12. |
In case of the installation the Council/Consultants word will be final. |
|
|
|
|